Get a Quote
How to Manually Calculate Chiller Capacity for Your Process

How to Manually Calculate Chiller Capacity for Your Process

Apr 04, 2019 Convert result into tons of chiller capacity. Divide Q (BTUs per hour) by 12,000 (the number of BTUs in one ton of cooling capacity). This yields the chiller capacity required to handle the process heat load in tons per hour: Example: 240,000/12,000= 20 tons/hr. Correct chiller tonnage for leaving water temp (LWT), if LWT is other than 50F:

More details
chiller capacity formula calculation...

chiller capacity formula calculation...

Apr 05, 2011 Q = Capacity in kW. M = Liquid mass flow rate kg/s. Cp = Liquid specific heat kJ/kg.K. DT = Liquid temperature difference C. Your mass flow rate is 0.166 kg/s. Q = 0.166 x 4.18 x (37-15) = 15.2 kW. You have to select a compressor which can give you 15.2 kW capacity at =3C evaporating and 50C condensing (if air cooled)

More details
Load Sizing Chillers - Temperature Corporation

Load Sizing Chillers - Temperature Corporation

Apr 05, 2018 When operating below 50 F you must decrease the rated chiller cooling capacity by 2% for every one degree F you operate below 50 F. To correct for 45 F operation you would divide the chiller rated cooling load by 0.9. See calculation: 100% – (2% x 5 F below 50 F) = 90% or 0.9.

More details
Glycol Chiller : Selecting the Correct Chiller - Cooling Towers

Glycol Chiller : Selecting the Correct Chiller - Cooling Towers

Assumes cold liquor tank is 2x Brewhouse Capacity and will be cooled by the chiller from 75F to 45 in 24 hours. Do You Have A Two Stage Wort Cooler? Yes No; Assumes dropping wort 20F (90F - 70F) in about 60 minutes while all other brewing loads are serviced. Cooling faster than in 60 minutes will increase the cooling requirement.

More details
How to Manually Calculate Chiller Capacity for Your Process

How to Manually Calculate Chiller Capacity for Your Process

Jan 27, 2022 Convert result into tons of chiller capacity: Divide Q (BTUs per hour) by 12,000 (the number of BTUs in one TR of cooling capacity). This yields the chiller capacity required to handle the process heat load in tons per hour: Example: 240,000/12,000= 20 TR.

More details
Calculating Cooling Load For Cold Stores

Calculating Cooling Load For Cold Stores

Lesson 35 Cooling And Heating Load Calculations March 19th, 2019 - a Cooling Load Factor is used for radiative component only b ... The value of cooling load factor always lies between 0 and 1 d The cooling load factor increases as the thermal capacity of the walls increase Ans a and c 7 Cold Stores Humidifier Solution Case Study Industrial ...

More details
How do you calculate gpm in a chilled water system?

How do you calculate gpm in a chilled water system?

Mar 12, 2020 If the chiller works at 25 horsepower: 25 x 3960 = 99,000. Multiply your answer by the pump's efficiency. If the pump works at 80 percent efficiency: 99,000 x 0.80 = 79,200. ... Calculate tons of cooling capacity Tons = BTU/hr. Oversize the chiller by 20% Ideal Size in Tons = Tons x 1.2. You have the ideal size for your needs. What GPM means?

More details
Chiller Sizing Guidelines Made Easy Conair

Chiller Sizing Guidelines Made Easy Conair

Mar 25, 2019 For example, to injection mold PET at a rate of 300 pounds per hour, the material calculation is 300 / 45 = 6.67 tons of chilling capacity per hour. For hydraulic motors, add 0.1 ton of chiller capacity per motor hp. For feed throat, add 0.5 ton of chiller capacity.

More details
Sizing Chillers Sizing Heat Exchangers How Much Cooling Capacity

Sizing Chillers Sizing Heat Exchangers How Much Cooling Capacity

Method A. Watts = [ (DT) F x K] / S. Where. DT= the F difference between incoming and outgoing tap water temperature of your instrument. Measure carefully using the same thermometer for both locations. K = Specific heat multiplied by the density of the fluid being circulated. Use 2,326 for water when calculating load in F.

More details
Sizing Chillers Sizing Heat Exchangers How Much Cooling Capacity

Sizing Chillers Sizing Heat Exchangers How Much Cooling Capacity

Method B. BTU/Hr=GPM x (DT) F x 500. Where. GPM of process fluid to be circulated. DT= the F difference between incoming and outgoing tap water temperature of your instrument. Measure carefully using the same thermometer for both locations. Fluid factor for 100% water=500.

More details
Calculating Process Chiller Loads SmartBlog

Calculating Process Chiller Loads SmartBlog

Nov 07, 2018 How to Calculate Chiller Tonnage – Formula. The final step to convert your answer into tons of chiller capacity is to divide your result, Q (BTUs per hour), by 12,000 (the number of BTUs in one ton of cooling capacity). This will give you, in tons per hour, the chiller capacity that is needed to handle the process heat load.

More details
Cooling Capacity of Recirculating Chillers Blog

Cooling Capacity of Recirculating Chillers Blog

Sep 23, 2019 W = average cooling power (W) V = total system liquid volume (L) T = temperature difference (C) K = liquid heat capacity (J/L/C) This formula can be helpful, but it’s a good idea to add on at least 20 percent more wattage to be on the safe side. After all, it’s highly unlikely that any system is going to be 100 percent efficient.

More details
How to Size a Chiller BV Thermal Systems

How to Size a Chiller BV Thermal Systems

The flow rate. General sizing formula: Calculate Temperature Differential (ΔTF) ΔTF = Incoming Water Temperature (F) – Required Chill Water Temperature. Calculate BTU/hr. BTU/hr. = Gallons per hr x 8.33 x ΔTF. Calculate tons of cooling capacity Tons = BTU/hr. 12,000. Oversize the chiller by 20% Ideal Size in Tons = Tons x 1.2.

More details
How to size a chiller - chiller cooling capacity caculation

How to size a chiller - chiller cooling capacity caculation

Therefore, the most important thing in the selection of industrial chillers is to obtain the rated cooling capacity. (2) The calculation method of the cooling capacity of the chiller. 1. Volume (liter) X number of temperature rise / heating time (minute) X 60 / 0.86 (coefficient) = (W) 2. Volume (tons or cubic meters) X number of temperature ...

More details
Plastic Processing Chiller - Capacity Calculation for Plastic ...

Plastic Processing Chiller - Capacity Calculation for Plastic ...

To determine the size of chiller you’ll need for your plastic process cooling application, follow this formula: Calculate the pounds of material per hour being processed. Determine how many pounds per hour are required for each ton of cooling capacity on Chart 1. Determine if the extruder or any auxiliary equipment will require chill water.

More details
Water Chiller Calculator - Estimate Cooling Tonnage

Water Chiller Calculator - Estimate Cooling Tonnage

Water Chiller Calculator; Estimate Chiller Cooling Tonnage. Water chillers are widely used to lower the temperature of water. This tool is useful in determining the cooling tonnage of the chiller. Flow Rate (LPH) Inlet Temp (C) Outlet Temp (C)